Input
- Voltage: 120 VAC (80 - 138 V at 100% load) 60-138 V at 40% load
- Capacity VA (W): 1000 VA (700 W)
- Frequency: 50/60 Hz auto sensing
- Power Factor: = 0.97
- Topology: True on-line, Double conversion, Input PF correction
Output
- Voltage: 120 VAC
- Frequency: 50/60 Hz auto sensing
- Wave Form: Sine wave, zero transfer time
- Load Power Factor: 0.7
- Efficiency AC/DC/AC: = 90%
- Auto Restart: Yes
- Start on Battery: Yes
- Rated Current: 8.3 A
- Overload Capacity: 110-150% for 30 sec, = 150% for 200 msec
- Crest Factor: 3:1 at full load
Battery
- Battery Type (UPS): (3) 12V 9AH/36V
- Backup Time: 7-11 min (internal batteries) to 18 hours using External Battery Packs (EBP)
- Extended Battery Packs: EBP1
- Battery Type (EBP): 2 strings of (3) 12V 9AH/36V
- Recharge Time: Typically < 4 hours
Physical
- Unit Dimensions (WxDxH): 17.3" x 17.7" x 3.4"
- Shipping Dimensions (WxDxH): 22.3" x 23.5" x 9.2"
- Unit Weight: 39.7 lbs
- Shipping Weight: 50.7 lbs
- Line Cord: 5-15P
-= Receptacles: (6) NEMA 5 - 15R
- Communication Interface: RS-232 or SNMP (optional card)
Environment
- Operating Temperature: 0° - 40°C (32° - 104°F)
- Audible Noise: < 50 dba at one meter
- Altitude: 6000 ft (1830 m) above sea level
- Warranty: Three years electronics / Three year batteries
- Approvals: North America UL cUL FCC
Indicators and Alarms
- LCD Visual Display: Input/output voltage & frequency, online mode, back up mode, battery capacity, load level
- Audible Alarm: Beep every 4 sec (on battery)
- UPS Fault: Continuous beeping sound and LCD display